Flammable Liquid Use and Storage Limits in Laboratories

The use and storage of flammable and combustible liquids may be necessary for some research laboratory operations. The National Fire Protection Association's NFPA 45-Standard on Fire Protection for Laboratories Using Chemicals sets limits on the use and storage of flammable and combustible liquids.

This fact sheet provides practical guidance to researchers on maximum allowable quantities, appropriate storage, and special ventilation considerations when contemplating the use of flammable and combustible liquids.

Maximum Allowable Quantities (MAQ)

The maximum allowable quantity of flammable and combustible liquids allowed in laboratories must be in accordance with the amount shown in the Tables 1 and 2.

Departments may request an exemption to exceed the maximum allowable quantities of flammable and combustible liquids in order to meet research needs. For an exemption, the department should contact F&S Campus Code Compliance & Fire Safety at (217) 265-5268 or via e-mail at rwild@illinois.edu.

Table 1: Maximum Quantities of Flammable and Combustible Liquids in Non-Sprinklered Labs

ClassMaximum Quantity per 100 sq. ft.Maximum Quantity per Laboratory UnitMaximum Quantity per 100 sq.ft.Maximum Quantity per Laboratory Unit
Without Flammable CabinetWith Flammable Cabinet
I*7.5L (2 gal)284 L (75 gal)15 L (4 gal)570 L (150 gal)
I*,II and III15 L (4 gal)380 L (100 gal)30 L (8 gal)760 L (200 gal)

Table 2: Maximum Quantities of Flammable and Combustible Liquids in Sprinklered Labs

ClassMaximum Quantity per 100 sq. ft.Maximum Quantity per Laboratory UnitMaximum Quantity per 100 sq. ft.Maximum Quantity per Laboratory Unit
Without Flammable CabinetWith Flammable Cabinet
I*7.5L (2 gal)570 L (150 gal)15 L (4 gal)1136 L (300 gal)
I*, II and III15 L (4 gal)757 L (200 gal)30 L (8 gal)1515 L (400 gal)

*This category includes Class I flammable liquids and liquefied flammable gases.

Flammable Liquid Storage Cabinet

Flammable Storage Cabinets

A Flammable Storage Cabinet may be required depending upon:

  • The class of flammable or combustible liquid

  • The total quantity of flammable or combustible liquid

  • The location of the flammable or combustible liquid

Venting Flammable Storage Cabinets

It is not recommended to vent flammable storage cabinets. Doing so could reduce the cabinet's fire protection effectiveness. However, if researchers choose to vent their cabinets in order to reduce odorous vapors, the following criteria must be followed:

  • Mechanical exhaust ventilation must be utilized. Exhaust must be discharged above the roof using an existing lab exhaust system or an independent system.

  • The cabinet must be vented from the bottom with fresh air being supplied from the top. The flame arrestor must remain in both the lower and upper bung holes. The bung holes should be regularly inspected and cleaned to prevent them from becoming blocked.

  • The exhaust duct provided must be a material of equivalent strength (or better) as the material used for the cabinet's construction (a minimum of 18 gauge sheet steel). The exhaust duct must also be a material compatible with the liquids stored inside the cabinet.

  • The exhaust duct must be welded. The use of stove pipe, dryer vent and PVC is prohibited.

Other Considerations Concerning Flammable Storage Cabinets

  • Flammable Storage Cabinets should never be located by exit doors.

  • Flammable Storage Cabinets must be listed by Factory Mutual, Underwriter's Laboratory or other qualified testing agencies.

  • Materials stored within Flammable Storage Cabinets should be compatible with the cabinet's design and construction.

  • Flammable Storage Cabinets must be clearly labeled with a sign that reads: "Flammable – Keep Fire Away"

  • Flammable Storage Cabinets should not be used to store corrosives, as they may corrode the cabinet and are incompatible with organic solvents.

Please contact Ryan Wild at F&S Campus Code Compliance & Fire Safety at 265-5268 or rwild@illinois.edu with questions concerning the use and/or limitations of flammable storage cabinets.

Definitions

Flammable Liquids – Liquids with a flash point below 100°F and a vapor pressure that does not exceed 40 psi at 100°F. Flammable liquids are subdivided as follows:

Flammable Liquid ClassDefinitionExamples
IALiquids with flash points below 73°F and boiling points below 100°FDiethyl ether n-Pentane Acetaldehyde
IBLiquids with flash points below 73°F and boiling points at or above 100°FAcetone Acetonitrile Ethanol(>50% if aqueous)
ICLiquids with flash points at or above 73°F and below 100°FIsopropyl alcohol Turpentine Xylenes

Combustible Liquids – Liquids with a flash point above 100°F. Combustible liquids are subdivided as follows:

Combustible Liquid ClassDefinitionExamples
IILiquids with flash points at or above 100°F and below 140°FAcetic acid Kerosene
IIIALiquids with flash points at or above 140°F and below 200°FEthanolamine DMSO Aniline
IIIBLiquids with flash points above 200°FEthylene glycol Benzyl alcohol

References

  • National Fire Protection Association (2004), NFPA 45: Fire Protection for Laboratories Using Chemicals. Batterymarch, PA: NFPA

  • National Fire Protection Association (1996), NFPA 30: Flammable and Combustible Liquid Code. Batterymarch, PA: NFPA

  • Occupational Safety and Health Administration (1996). General Industry Safety and Health Standards 29CFR 1910.106. Washington, DC: Bureau of National Affairs, Inc.