The use and storage of flammable and combustible liquids may be necessary for some research laboratory operations. The National Fire Protection Association's NFPA 45-Standard on Fire Protection for Laboratories Using Chemicals sets limits on the use and storage of flammable and combustible liquids.
This fact sheet provides practical guidance to researchers on maximum allowable quantities, appropriate storage, and special ventilation considerations when contemplating the use of flammable and combustible liquids.
The maximum allowable quantity of flammable and combustible liquids allowed in laboratories must be in accordance with the amount shown in the Tables 1 and 2.
Departments may request an exemption to exceed the maximum allowable quantities of flammable and combustible liquids in order to meet research needs. For an exemption, the department should contact F&S Campus Code Compliance & Fire Safety at (217) 265-5268 or via e-mail at rwild@illinois.edu.
| Class | Maximum Quantity per 100 sq. ft. | Maximum Quantity per Laboratory Unit | Maximum Quantity per 100 sq.ft. | Maximum Quantity per Laboratory Unit |
|---|---|---|---|---|
| Without Flammable Cabinet | With Flammable Cabinet | |||
| I* | 7.5L (2 gal) | 284 L (75 gal) | 15 L (4 gal) | 570 L (150 gal) |
| I*,II and III | 15 L (4 gal) | 380 L (100 gal) | 30 L (8 gal) | 760 L (200 gal) |
| Class | Maximum Quantity per 100 sq. ft. | Maximum Quantity per Laboratory Unit | Maximum Quantity per 100 sq. ft. | Maximum Quantity per Laboratory Unit |
|---|---|---|---|---|
| Without Flammable Cabinet | With Flammable Cabinet | |||
| I* | 7.5L (2 gal) | 570 L (150 gal) | 15 L (4 gal) | 1136 L (300 gal) |
| I*, II and III | 15 L (4 gal) | 757 L (200 gal) | 30 L (8 gal) | 1515 L (400 gal) |
*This category includes Class I flammable liquids and liquefied flammable gases.

A Flammable Storage Cabinet may be required depending upon:
The class of flammable or combustible liquid
The total quantity of flammable or combustible liquid
The location of the flammable or combustible liquid
It is not recommended to vent flammable storage cabinets. Doing so could reduce the cabinet's fire protection effectiveness. However, if researchers choose to vent their cabinets in order to reduce odorous vapors, the following criteria must be followed:
Mechanical exhaust ventilation must be utilized. Exhaust must be discharged above the roof using an existing lab exhaust system or an independent system.
The cabinet must be vented from the bottom with fresh air being supplied from the top. The flame arrestor must remain in both the lower and upper bung holes. The bung holes should be regularly inspected and cleaned to prevent them from becoming blocked.
The exhaust duct provided must be a material of equivalent strength (or better) as the material used for the cabinet's construction (a minimum of 18 gauge sheet steel). The exhaust duct must also be a material compatible with the liquids stored inside the cabinet.
The exhaust duct must be welded. The use of stove pipe, dryer vent and PVC is prohibited.
Flammable Storage Cabinets should never be located by exit doors.
Flammable Storage Cabinets must be listed by Factory Mutual, Underwriter's Laboratory or other qualified testing agencies.
Materials stored within Flammable Storage Cabinets should be compatible with the cabinet's design and construction.
Flammable Storage Cabinets must be clearly labeled with a sign that reads: "Flammable – Keep Fire Away"
Flammable Storage Cabinets should not be used to store corrosives, as they may corrode the cabinet and are incompatible with organic solvents.
Please contact Ryan Wild at F&S Campus Code Compliance & Fire Safety at 265-5268 or rwild@illinois.edu with questions concerning the use and/or limitations of flammable storage cabinets.
Flammable Liquids – Liquids with a flash point below 100°F and a vapor pressure that does not exceed 40 psi at 100°F. Flammable liquids are subdivided as follows:
| Flammable Liquid Class | Definition | Examples |
|---|---|---|
| IA | Liquids with flash points below 73°F and boiling points below 100°F | Diethyl ether n-Pentane Acetaldehyde |
| IB | Liquids with flash points below 73°F and boiling points at or above 100°F | Acetone Acetonitrile Ethanol(>50% if aqueous) |
| IC | Liquids with flash points at or above 73°F and below 100°F | Isopropyl alcohol Turpentine Xylenes |
Combustible Liquids – Liquids with a flash point above 100°F. Combustible liquids are subdivided as follows:
| Combustible Liquid Class | Definition | Examples |
|---|---|---|
| II | Liquids with flash points at or above 100°F and below 140°F | Acetic acid Kerosene |
| IIIA | Liquids with flash points at or above 140°F and below 200°F | Ethanolamine DMSO Aniline |
| IIIB | Liquids with flash points above 200°F | Ethylene glycol Benzyl alcohol |
National Fire Protection Association (2004), NFPA 45: Fire Protection for Laboratories Using Chemicals. Batterymarch, PA: NFPA
National Fire Protection Association (1996), NFPA 30: Flammable and Combustible Liquid Code. Batterymarch, PA: NFPA
Occupational Safety and Health Administration (1996). General Industry Safety and Health Standards 29CFR 1910.106. Washington, DC: Bureau of National Affairs, Inc.